SKU: FLK-1662 SCH
The 1662, one of our multifunction testers, tests to all local regulations & provides test results for complete documentation. Learn more today!
List price. Volume pricing available.
The 1662, one of our multifunction testers, tests to all local regulations & provides test results for complete documentation. Learn more today!
The Fluke 1662 SCH Installation Tester with Mem Schuko # FLK-1662 SCH is manufactured by Fluke. Valley Instrument Service is an authorized Fluke dealer offering full sales support, NIST-traceable calibration, and expert technical assistance.
Our team can help with product selection, specs, pricing, and application support.
Contact Us or Call (661) 327-8681| General | AC voltage measurement |
| Range | 500 V |
| Resolution | 0.1 V |
| Accuracy 45 Hz – 66 Hz | 0.8% + 3 |
| Input impedance | 360 kΩ |
| Overload protection | 660 V rms |
| Range (autoranging) | 20 Ω / 200 Ω / 2000 Ω |
| Open Circuit Voltage | >4 V |
| Accuracy of test voltage (at rated test current) | +10%, -0% |
| Test voltage | 100 V250 V500 V1000 V |
| Insulation resistance range | 20 MΩ / 50 MΩ20 MΩ / 100 MΩ20 MΩ / 200 MΩ20 MΩ / 200 MΩ / 500 MΩ20 MΩ / 200 MΩ / 1000 MΩ |
| Test current | 1 mA @ 50 kΩ1 mA @ 100 kΩ1 mA @ 250 kΩ1 mA @ 500 kΩ1 mA @ 1 MΩ |
| Computation | Prospective earth fault current (PEFC) or Prospective short circuit current (PSC) determined by dividing measured mains voltage by measured loop (L-PE) resistance or line (L-N) resistance, respectively. |
| RCD Type | A4, AC¹, G², S³ |
| Notes | ¹Responds to AC²General, no delay³Time delay4Responds to pulsed signal5Responds to smooth DC signal |
| Current settings¹ | 10-30-100-300-500-1000 mA – VAR10-30-100 mA |
| Multiplier | x ½, x 1x 5 |
| RCD Type G | 310 ms50 ms |
| RCD Type S | 510 ms160 ms |
| Measurement range | RCD/FI-Tripping Current Measurement/Ramp Test (IΔN) |
| Current range | 30% to 110% of RCD rated current¹ |
| Step size | 10% of IΔN² |
| Type G | 300 ms/step |
| Type S | 500 ms/step |
| Measurement accuracy | ±5% |
| Specified trip current ranges (EN 61008-1) | 50% to 100% for Type AC35% to 140% for Type A (>10 mA)35% to 200% for Type A (≤10 mA)50% to 200% for Type B²5% for Type B |
| Dwell time | Phase Sequence Indication |
| Icon | Phase Sequence indicator is active. |
| Size (L x W x H) | 10 x 25 x 12.5 cm |
| Weight (incl. batteries) | 1.3 (kg) |
| Battery size, quantity | Type AA, 6 ea. |
| Sealing | IP-40 |
| Safety | Complies with EN/IEC 61010-1 and EN/IEC 61010-2-034 |
| Overvoltage | CAT III / 500V; CAT IV 300V |
| Performance | EN61557-1 to EN61557-7 and EN61557-10 |
This product is part of a family with 2 models. Select a model below to view details.
| Model | Price | |
|---|---|---|
FLK-1662 SCHCurrent | Request Quote | Viewing |
FLK-1662 US | Request Quote | View Details → |

Multifunction installation tester with RCD Type B testing. Tests to local regulations and provides results for complete documentation. US (NEMA) plug.
Replacement main test cord for Fluke 1660 series multifunction installation testers. North America version.

Multifunction installation tester with TruTest reporting software. Insulation resistance, loop/line resistance, voltage, frequency, and polarity testing. Schuko (CEE 7/7) plug.

Multifunction installation tester with Fluke Connect wireless and TruTest reporting software. Insulation resistance, earth ground, loop/line resistance, voltage, frequency, and polarity. Schuko (CEE 7/7) plug.