SKU: FLUKE-355
Versatile and rugged for high currents up to 2000A AC/DC. Extra wide jaw easily clamps around large conductors found in high-current applications.
List price. Volume pricing available.
Versatile and rugged for high currents up to 2000A AC/DC. Extra wide jaw easily clamps around large conductors found in high-current applications.
The Fluke 355 AC/DC TRMS Clamp Meter, 2000A # FLUKE-355 is manufactured by Fluke. Valley Instrument Service is an authorized Fluke dealer offering full sales support, NIST-traceable calibration, and expert technical assistance.
Our team can help with product selection, specs, pricing, and application support.
Contact Us or Call (661) 327-8681| General | Electrical Specifications |
| Range | 40 A / 400 A / 1400 AC rms |
| Resolution | 10 mA / 100 mA / 1 A |
| Accuracy | 40 A: 1.5% rdg + 15 digits 400 A: 1.5% rdg + 5 digits 1400 A: 1.5% rdg + 5 digits |
| Trigger level for Inrush | 0.50 A / 5.0 A / 5 A |
| Trigger level for Hz filter OFF | 2.50 A / 2.5 A / 8 A |
| Trigger level for Hz filter ON | 0.50 A / 2.5 A / 8 A |
| Crest Factor1 | 2 @ 33 A, 2.4 @ 27 A2 @ 330 A, 2.4 @ 270 A2 @ 1000 A, 2.4 @ 833 A |
| Continuity beeper | On at ≤ 30 ΩOff at ≥ 100 Ω |
| Measurement range | 5.0 Hz to 1 kHz |
| Accuracy – 5.0 Hz to 100 Hz | 0.2% + 2 counts |
| Accuracy – 100.1 Hz to 1 kHz | 0.5% + 5 counts |
| Trigger level | Refer to current and voltage tables |
| Frequency measurement | 1. Add 2% to error spec for CF > 2 |
| Batteries | Six 1.5 V AA NEDA 15 A or IEC LR6 |
| Battery life (with typical usage, backlight off) | 100 hours |
| Test leads | Rated to 1000 V |
| Weight | .814 kg (1.8 lb) |
| Jaw size | 58 mm (2.28 in) |
| Dimensions (L x W x D) | 300 x 98 x 52 mm (12 x 3.75 x 2 in) |
| Safety rating | IEC 61010-2-032, 600 V CAT IV, 1000 V CAT III |
| Operating temperature | 32°F to +122°F (0°C to +50°C) |
| Storage temperature | -4°F to 140°F (-20°C to +60°C) |
| Operating humidity | 0 to 95% (non-condensing) |
| Operating altitude | 2000 m |
| Storage altitude | 10,000 m |
| IP rating | 42 (indoor use only) |
| Drop test requirements | 1 m |
| EMI, RFI, EMC | FCC part 15, IEC/EN 61326-1:1997 class BIEC/EN 61326:1997 3 V/m, performance criteria B, EN61325 |
| Current | 0.1% of reading per °C outside 22°C to 24°C |
| Voltage | 0.1% of reading per °C outside 22°C to 24°C |

Get the right HVAC multimeter for accurate temperature & microamp measurements. The Fluke 116 digital multimeter has everything you need in an HVAC meter.